Model HEP
HEP
model High Efficiency Pressure is a single wall stainless
steel chimney. This chimney is UL listed for positive pressure applications
up to 60" water column.
Features
- Wall: AL29-4C (26ga - 6" (152mm) to 12" (305mm) diameter;
24ga - 12" (305mm) to 48" (1219mm) diameter)
- Continuous plasma-weld
- Full range of accessories including elbows, fittings, guides and supports.

Applications
- Models HEP, HEPL and HEPL2
venting systems are primarily intended to be installed in fire resistive,
non combustible surroundings or in unenclosed installation. They are
not intended for use in one or two-family dwellings. (CAUTION: Do not
enclose this venting system in chase or passageway made of wood or other
combustible material.)
- Where the venting system extends through any zone of a building outside
the area in which the heating appliance connected to it is located,
it shall be provided with an enclosure having a fire resistance rating
equal to or greater than the fire rating of the floor, wall or roof
assemblies through which it passes.
- Models HEP, HEPL and HEPL2
venting systems may penetrate a combustible roof or wall using the Ventilated
Roof Flashing assembly. For wall penetrations, the use of the Wall Firestop
assembly is required. This is the only part intended for use with combustible
construction. All other parts, such as Anchor Plate and Wall Support,
Wall Guide and Floor Guide are for attachment to non-combustible construction.
- Where, according to local code, no chase enclosure is necessary, models
HEP, HEPL and HEPL2
may be placed adjacent to or on each pipe section and in the individual
listing; see "CLEARANCES". Contact local building or fire
officials about restrictions and installation inspection in your area.

Listings
CHEMINEE LINING.E inc. venting systems models HEP,
HEPL and HEPL2 are listed by Underwriters
Laboratories inc. (UL) under file MH26661 and tested in accordance
with UL 1738 Standard for Venting Categories II, III
and IV appliances.
UL 1738
| Models HEP • HEPL • HEPL2 |
Temperature |
Size |
| Categories II, III and IV appliances |
550°F continuous |
6" to 48" ID |

Sample Specification (Boiler Exhaust)
The chimney and flue must meet UL (Underwriters Laboratories inc.) and
c-UL (Underwriters Laboratories of Canada Inc.) standards and carry the
appropriate approval labels. The maximum temperature must be 550°F
(288°C) for continuous operation.
The chimney and flue components must be of double wall construction and
properly designed for positive pressure exhaust. The inner wall must be
of 24 gauge AL29-4C stainless steel, with continuous plasma welds. The
outer wall must be of 24 gauge 304 stainless steel. A high temperature
insulation (2 in.) must be installed between walls. The jointing must
be made using the assembly band, the finishing band and the appropriate
sealing material, as supplied by the manufacturer. Quality required: Model
HEPL2.
All components must be installed according to the manufacturer recommendations
and must meet the NFPA and local safety code requirements.

Components
Small Size 6" – 14"
Large Size 16" – 48"
Special
Parts

Weights and Clearances
| HEP • HEPL • HEPL2 |
LINEAR WEIGHT |
| I.D. |
O.D. |
AREA |
HEP |
HEPL |
HEPL2 |
| in |
mm |
in |
mm |
in2 |
1000mm2 |
lb/ft |
kg/m |
lb/ft |
kg/m |
lb/ft |
kg/m |
| 6 |
152 |
10 |
254 |
28 |
18,2 |
5,4 |
8 |
8,8 |
13,1 |
8,8 |
13,1 |
| 8 |
203 |
12 |
305 |
50 |
32,4 |
6,8 |
10,1 |
11,0 |
16,4 |
11,0 |
16,4 |
| 10 |
254 |
14 |
356 |
79 |
50,7 |
8,2 |
12,2 |
13,3 |
19,8 |
13,3 |
19,8 |
| 12 |
305 |
16 |
406 |
113 |
73,0 |
9,6 |
14,3 |
15,6 |
23,2 |
15,6 |
23,2 |
| 14 |
356 |
18 |
457 |
154 |
99,3 |
11,0 |
16,4 |
17,8 |
26,5 |
17,8 |
26,5 |
| 16 |
406 |
20 |
508 |
201 |
129,7 |
12,5 |
18,5 |
20,1 |
29,9 |
20,1 |
29,9 |
| 18 |
457 |
22 |
559 |
254 |
164,2 |
13,9 |
20,6 |
22,4 |
33,3 |
22,4 |
33,3 |
| 20 |
508 |
24 |
610 |
314 |
202,7 |
15,3 |
22,7 |
24,6 |
36,6 |
24,6 |
36,6 |
| 22 |
559 |
26 |
660 |
380 |
245,2 |
16,7 |
24,8 |
26,9 |
40,0 |
26,9 |
40,0 |
| 24 |
610 |
28 |
711 |
452 |
291,9 |
18,1 |
26,9 |
29,2 |
43,4 |
29,2 |
43,4 |
| 26 |
660 |
30 |
762 |
531 |
342,5 |
19,5 |
29,1 |
31,4 |
46,7 |
31,4 |
46,7 |
| 28 |
711 |
32 |
813 |
616 |
397,3 |
20,9 |
31,2 |
33,7 |
50,1 |
33,7 |
50,1 |
| 30 |
762 |
34 |
864 |
707 |
456,0 |
22,4 |
33,3 |
36,0 |
53,6 |
36,0 |
53,6 |
| 32 |
813 |
36 |
914 |
804 |
518,9 |
23,8 |
35,4 |
38,2 |
56,8 |
38,2 |
56,8 |
| 34 |
864 |
38 |
965 |
908 |
585,8 |
25,2 |
37,5 |
40,5 |
60,3 |
40,5 |
60,3 |
| 36 |
914 |
40 |
1016 |
1018 |
656,7 |
26,6 |
39,6 |
42,8 |
63,7 |
42,8 |
63,7 |
| 38 |
965 |
42 |
1067 |
1134 |
731,7 |
28,8 |
41,7 |
45,0 |
67,0 |
45,0 |
67,0 |
| 40 |
1016 |
44 |
1118 |
1257 |
810,7 |
29,4 |
43,8 |
47,3 |
70,4 |
47,3 |
70,4 |
| 42 |
1067 |
46 |
1168 |
1385 |
893,8 |
30,8 |
45,9 |
49,6 |
73,8 |
49,6 |
73,8 |
| 44 |
1118 |
48 |
1219 |
1521 |
981,0 |
32,3 |
48,0 |
51,8 |
77,1 |
51,8 |
77,1 |
| 46 |
1168 |
50 |
1270 |
1662 |
1072,2 |
33,7 |
50,1 |
54,1 |
80,5 |
54,1 |
80,5 |
| 48 |
1219 |
52 |
1320 |
1810 |
1167,5 |
35,1 |
52,2 |
56,4 |
83,9 |
56,4 |
83,9 |
| MINIMUM CLEARANCE AIR SPACE TO COMBUSTIBLE CONSTRUCTION |
| INSIDE DIAMETER |
HEP |
HEPL |
HEPL2 |
| |
|
HORIZ.
UNENCL. |
HORIZ.
UNENCL. |
HORIZ.
UNENCL. |
HORIZ.
UNENCL. |
HORIZ.
UNENCL. |
HORIZ.
UNENCL. |
| in |
mm |
in |
mm |
in |
mm |
in |
mm |
in |
mm |
in |
mm |
in |
mm |
| 6" |
152 |
1.5 |
38 |
3 |
76 |
0,5 |
12 |
1 |
25 |
0,5 |
12 |
1 |
25 |
| 8" to 10" |
203 to 254 |
2 |
51 |
3 |
76 |
1,5 |
38 |
1 |
25 |
1 |
25 |
1 |
25 |
| 12" to 14" |
305 to 356 |
3 |
76 |
4 |
102 |
2 |
51 |
1,5 |
38 |
1,5 |
38 |
1,5 |
38 |
| 16" to 20" |
406 to 508 |
4 |
102 |
5 |
127 |
3 |
76 |
3 |
76 |
2 |
51 |
2 |
51 |
| 22" to 24" |
559 to 610 |
5 |
127 |
6 |
152 |
4 |
102 |
4 |
102 |
3 |
76 |
3 |
76 |
| 26" to 28" |
660 to 711 |
– |
– |
– |
– |
5 |
127 |
4 |
102 |
– |
– |
– |
– |
| 26" to 30" |
660 to 762 |
6 |
152 |
6 |
152 |
– |
– |
– |
– |
4 |
102 |
3 |
76 |
| 30" to 32" |
762 to 813 |
7 |
178 |
7 |
178 |
6 |
152 |
5 |
127 |
– |
– |
4 |
102 |
| 32" to 36" |
813 to 914 |
– |
– |
7 |
178 |
– |
– |
– |
– |
5 |
127 |
4 |
102 |
| 34" to 38" |
864 to 965 |
– |
– |
– |
– |
7 |
178 |
6 |
152 |
– |
– |
– |
– |
| 34" to 44" |
864 to 1118 |
8 |
203 |
– |
– |
– |
– |
– |
– |
– |
– |
– |
– |
| 38" to 40" |
965 to 1016 |
– |
– |
– |
– |
– |
– |
– |
– |
6 |
152 |
5 |
127 |
| 38" to 42" |
965 to 1067 |
9 |
229 |
8 |
203 |
– |
– |
– |
– |
– |
– |
– |
– |
| 40" to 44" |
1016 to 1118 |
– |
– |
– |
– |
– |
– |
– |
– |
– |
– |
5 |
127 |
| 42" to 48" |
1067 to 1219 |
– |
– |
– |
– |
– |
– |
– |
– |
7 |
178 |
– |
– |
| 44" to 48" |
1118 to 1219 |
10 |
254 |
9 |
229 |
9 |
229 |
8 |
203 |
– |
– |
6 |
152 |
Minimum opening when installing a chimney through a floor or wall made
of combustible construction.
O.D. + 2 X (min. clearance air space) Ex. : HEPL2, B.H.A.,
O.D. = 12” -› 12” + (2 X 2”) = 16”
Minimum opening when installing a chimney through a floor or wall made
of non combustible construction.
O.D. + 1” Ex. : HEPL2, B.H.A., O.D. = 12”
-› 12” + 1” = 13”

| |