Phone: 450.625.6060 / 1.866.625.6060

 

 

Factory Built Chimney

 
 

 

 

Model IPPL2

 

Product Brochure


IPPL2 model Industrial Positive Pressure is a double wall stainless steel chimney with 2" mineral fiber insulation. This chimney is UL listed for positive pressure applications up to 60" water column.

Features

  • Inner wall: standard 304 2B stainless steel (20 gauge - 6" to 40" diameter; 18 gauge - 42" to 48" diameter)
  • Outer wall: standard 304 2B stainless steel (24 gauge - 6" to 40" diameter; 20 gauge - 42" to 48" diameter)
  • Continuous plasma-weld
  • Full range of accessories including elbows, fittings, guides and supports.

Applications

  1. Building Heating Appliance Chimney Listing (1000°F Chimney Listing) – under this category, models IPPL, IPPL2 and IPPL2F, have been determined suitable for venting flue gases at a temperature not exceeding 540°C (1000°F) under continuous operating conditions, from gas, liquid, oil or solid fuel fired appliances.
  2. Building Heating Appliance Chimneys are suitable for use with Building Heating Appliances and Low Heat Appliances as described in the Chimney Selection Chart of National Fire Protection Association (NFPA) Standard No. 211.
  3. 1400°F Chimney Listing – under this category, models IPPL and IPPL2F, have been determined suitable for venting flue gases at a temperature not exceeding 760°C (1400°F) under continuous operating conditions. As such, they are suitable for use with ovens and furnaces as described in the Chimney Selection Chart of NFPA No. 211, in addition to other applications.
Criteria Grease Duct Restaurant BHA Chimney 1400°F Chimney
Application
  • Cooking Appliances
  • Ventilation Hoods
  • Restaurant Grease Ducts
  • Pizza Oven Exhausts
  • Low and High Pressure Steam Boilers
  • Diesel and Turbine
    Exhausts
  • Building Heating Equipment
  • Industrial furnaces
  • Processing Equipment
  • Kilns and Ovens
  • Diesel and Turbine Exhaust
  • Incinerator
  • Coffee Roaster
Continuous operating
temperature
500°F 1000°F 1400°F
IPPL Yes Yes Yes
IPPL2 N/A Yes N/A
IPPL2F Yes Yes Yes

Weights and Clearances

IPPL • IPPL2 • IPPL2F LINEAR WEIGHT
I.D. O.D. AREA IPPL IPPL2 IPPL2F
in mm in mm in2 1000 mm2 lb/ft kg/m lb/ft kg/m lb/ft kg/m
6 152 10 254 28 18.2 5.4 8.0 8.8 13.1 8.8 13.1
8 203 12 305 50 32.4 6.8 10.1 11.0 16.4 11.0 16.4
10 254 14 356 79 50.7 8.2 12.2 13.3 19.8 13.3 19.8
12 305 16 406 113 73.0 9.6 14.3 15.6 23.2 15.6 23.2
14 356 18 457 154 99.3 11.0 16.4 17.8 26.5 17.8 26.5
16 406 20 508 201 129.7 12.5 18.5 20.1 29.9 20.1 29.9
18 457 22 559 254 164.2 13.9 20.6 22.4 33.3 22.4 33.3
20 508 24 610 314 202.7 15.3 22.7 24.6 36.6 24.6 36.6
22 559 26 660 380 245.2 16.7 24.8 26.9 40.0 26.9 40.0
24 610 28 711 452 291.9 18.1 26.9 29.2 43.4 29.2 43.4
26 660 30 762 531 342.5 19.5 29.1 31.4 46.7 31.4 46.7
28 711 32 813 616 397.3 20.9 31.2 33.7 50.1 33.7 50.1
30 762 34 864 707 456.0 22.4 33.3 36.0 53.6 36.0 53.6
32 813 36 914 804 518.9 23.8 35.4 38.2 56.8 38.2 56.8
34 864 38 965 908 585.8 25.2 37.5 40.5 60.3 40.5 60.3
36 914 40 1016 1018 656.7 26.6 39.6 42.8 63.7 42.8 63.7
38 965 42 1067 1134 731.7 28.0 41.7 45.0 67.0 45.0 67.0
40 1016 44 1118 1257 810.7 29.4 43.8 47.3 70.4 47.3 70.4
42 1067 46 1168 1385 893.8 30.8 45.9 49.6 73.8 49.6 73.8
44 1118 48 1219 1521 981.0 32.3 48.0 51.8 77.1 51.8 77.1
46 1168 50 1270 1662 1072.2 33.7 50.1 54.1 80.5 54.1 80.5
48 1219 52 1320 1810 1167.5 35.1 52.2 56.4 83.9 56.4 83.9

 

MINIMUM CLEARANCE AIR SPACE TO COMBUSTIBLE CONSTRUCTION
MODEL IPPL   MODEL IPPL2 MODEL IPPL2F
Inside Diameter Clearance Inside Diameter Clearance Clearance
(1000°F and 1400°F)   (1000°F) (1000°F and 1400"F)  
6" to 12" 4" 6" to 12" 1" 1"
14" 5" 14" 1.5" 1.5"
16" to 18" 6" 16" to 18" 2" 2"
20" to 24" 7" 20" to 22" 3" 3"
26" to 28" 8" 24" to 26" 4" 4"
30" to 34" 9" 28" to 32" 5" 5"
36" to 38" 10" 34" to 36" 6" 6"
40" to 48" 11" 38" to 40" 7" 7"
    42" to 48" 8" 8"

Listings

CHEMINEE LINING.E inc. venting systems models IPPL, IPPL2 and IPPL2F are listed by Underwriters Laboratories, inc. (UL) under file MH26661 and tested in accordance with UL 103 Standard for Factory-Built Chimneys for Residential Type and Building Heating Appliances and the Canadian Standard for 540°C (1000°F) and 760°C (1400°F) industrial Chimneys CAN/ULC-C959. These models are also suitable for use in positive pressure applications up to 60” water column. Listings include the following chimney product categories and diameters..

UL 103

Models IPPL2 • IPPL2F Temperature Diameter
Building Heating Appliance Type Chimney 1000°F continuous 6" to 48" ID
1400°F Chimney (Models IPPL and IPPL2F only) 1400°F continuous 6" to 48" ID

CAN/ULC C-959

Models IPPL • IPPL2 • IPPL2F Temperature Diameter
Building Heating Appliance Type Chimney 1000°F continuous 6" to 48" ID
1400°F Chimney (Models IPPL and IPPL2F only) 1400°F continuous 6" to 48" ID

Sample Specification (Boiler Exhaust)

The chimney and flue must meet ULC (Underwriters Laboratories of Canada) and UL-103 (Underwriters Laboratories Inc.) section 22A for positive pressure exhaust system up to 60” water column and carry the appropriate approval labels. The chimney shall be listed by UL as a “B.H.A.” (Building heating appliance) chimney for continuous operation up to 1000°F (540°C) maximum. For applications above 1000°F (540°C), the chimney shall be listed by UL as a “1400°F chimney” for continuous operation up to 1400°F (760°C) maximum.

The chimney and flue components must be of double wall construction and properly designed for positive pressure exhaust. The inner wall must be of 20 gauge (18 gauge – 42” to 48” diameter) 304 stainless steel, with continuous plasma welds. The outer wall must be of 24 gauge (20 gauge – 42” to 48” diameter) 304 stainless steel. A high temperature insulation (2 in.) must be installed between walls. The jointing must be made using an assembly band, a finishing band and an appropriate sealing material, as supplied by the manufacturer. Quality required : Model IPPL2.

All components must be installed according to the manufacturer recommendations and must meet the NFPA and local safety code requirements.

Components

 

 
  © Cheminée Lining.e inc.